Instrumentation Cable complying to British Standard

 

The cables may be designed with or without screens and optionally incorporating wire armour. These cables are suitable for operation at voltages up to and including 300 V r.m.s core to earth and 500 V r.m.s. core-to-core.

There are three categories of instrumentation cables

A) Polyethylene insulated and PVC sheathed
(These cables are not recommended for underground burial)

B) Polyethylene insulated, polyethylene bedded, steel wire armoured and PVC sheathed.

C) PVC insulated, armoured/non armoured and PVC sheathed

 

Instrumentation cable made to British Standard

 

Construction

Conductors
Conductors shall be plain annealed copper wire in accordance with BS 6360

Insulation
Polyethylene (PE) Type 03 or Polyvinyl Chloride (PVC) Type TI1

Pair Identification
Coloured insulation as per Table 11 for PVC insulated cable and Table 12 for the PE insulated cable

Screen
Individual pair screen - When required, each pair shall have a laminated screening tape applied with the metallic side down, in electrical contact with a tinned annealed stranded copper drain wire run longitudinally over the non-hygroscopic binder tape.

Collective screen - When required, a laminated screening tape shall be applied with the metallic side down, in electrical contact with a tinned annealed stranded copper drain wire run longitudinally over the non-hygroscopic binder tape.

Bedding
A layer of either PE or PVC shall be extruded over the binder tape.

Armour
For armoured cable, a single layer of galvanized steel wire armoured shall be spirally applied over the bedding

Outer protection
Extruded PVC

 

Electrical Characteristics

Details of conductors and insulation thickness
Nominal sectional area Construction Nominal diameter Max. conductor Resistance at 20°C Thickness of insulation Max Core diameter
No. of wire/diameter Nominal Minimum
(mm2) (No./mm) (mm) (ohm/km) (mm) (mm) (mm)
0.50 1/0.80 0.80 36.80 0.50 0.50 1.90
1.00 1/1.13 1.13 18.40 0.60 0.50 2.45
1.50 7/0.53 1.59 12.30(12.10 for multicore) 0.60 0.50 3.00

 

Note
As BS 6360 resistance values only allow for multicore cables, an additional 2% of the maximum resistance has been allowed for cables of multipair construction

Maximum mutual capacitance
Cables without screens 75 pF/m
Cables with only collective screens
(except 1-pair and 2-pair)
75 pF/m
1-pair and 2-pair cables collectively screened and all cables with individually screened pairs 115pF/m

 

If you need further technical specifications, email us.

Top ^

Back to Products page >

 

 

 

 

 

 

Sales Office:
Unit 8.2, Level 8 Building A
Peremba Square, Saujana Resort Seksyen U2
40150 Shah Alam
Selangor Darul Ehsan,
Malaysia.

Tel: +6 03 7845 7788
Fax: +6 03 7845 2258 / 3348

 

Main Office/Factory:
Lot 1385
Tikam Batu Industrial Estate,
Tikam Batu,
08600 Sungai Petani,
Kedah Darulaman, Malaysia.

Tel: 604-438 9988
Fax: 604-438 9110